Basic Information
表格
| Item | Specification |
|---|---|
| Model | ACS580-04-585A-4 |
| Product Series | ABB ACS580 LV AC General Purpose Drive |
| Frame Size | R10 |
| Mounting Type | Module type for cabinet installation |
| Protection Degree | IP00 |
| Cooling | Force-cooled |
Electrical Ratings – Input
表格
| Parameter | Value |
|---|---|
| Nominal Input Voltage | 380–480 V, 3-phase |
| Voltage Range | 340–560 V |
| Input Frequency | 47.5–63 Hz |
| Input Phases | 3-phase |
| Input Harmonics | Built-in DC choke, C3 EMC filter |
Electrical Ratings – Output
表格
| Parameter | Value |
|---|---|
| Nominal Output Current (Typical Duty / LD) | 585 A |
| Heavy Duty Output Current (HD) | 429 A |
| Maximum Peak Output Current | 730 A (for 2 s) |
| Output Voltage | 0–input voltage (0–480 V) |
| Output Frequency Range | 0–300 Hz |
| Normal Duty Power (LD, 400 V/50 Hz) | 315 kW |
| Heavy Duty Power (HD, 400 V/50 Hz) | 250 kW |
| Typical Motor Rating (480 V/60 Hz) | 450 HP |
| Apparent Power | 405 kVA |
| Overload Capability (LD) | 110% for 60 s |
| Overload Capability (HD) | 120% for 60 s |
Efficiency & Thermal
表格
| Parameter | Value |
|---|---|
| Typical Efficiency (100% load, 50 Hz) | ~97.5% |
| Efficiency Class | IE2 |
| Standby Power Loss | 423 W |
| Ambient Temperature (Operation) | -10 °C to +40 °C (no derating) |
| Ambient Temperature (Derating) | Above 40 °C, 1% per °C up to 55 °C |
| Storage Temperature | -40 °C to +70 °C |
Physical Data
表格
| Parameter | Value |
|---|---|
| Dimensions (H × W × D) | 1465 × 350 × 529 mm |
| Net Weight | 161 kg |
| Acoustic Noise | 72 dB(A) |
Control & Interfaces
表格
| Item | Specification |
|---|---|
| Safe Torque Off (STO) | PL d / Cat.3, EN ISO 13849-1 |
| Analog Inputs | 2 × (0–10 V / 0–20 mA) |
| Analog Outputs | 2 × (0–10 V / 0–20 mA) |
| Digital Inputs | 6 × 24 VDC |
| Digital Outputs | 3 × relay (250 VAC / 30 VDC, 1 A) |
| Built-in Communication | RS-485 (Modbus RTU), USB |
| Optional Fieldbus | PROFINET, PROFIBUS, EtherNet/IP, Modbus TCP, CANopen, DeviceNet |
Environmental & Protection
表格
| Parameter | Value |
|---|---|
| Operating Altitude | Up to 1000 m (no derating) |
| Humidity | 5–95% RH, non-condensing |
| Protection Functions | Overcurrent, overvoltage, undervoltage, overtemperature, earth fault, short circuit, phase loss, motor stall |