Main |
Range of product |
Altivar Process ATV900 |
Device application |
Industrial application |
Product or component type |
Variable speed drive |
Product destination |
Synchronous motors |
Asynchronous motors |
Product specific application |
Process for industrial |
Variant |
Standard version |
With braking chopper |
Network number of phases |
3 phases |
Single phase |
Mounting mode |
Wall mount |
Communication port protocol |
Ethernet IP/Modbus TCP |
Modbus |
[Us] rated supply voltage |
380…480 V – 15…10 % |
Continuous output current |
211 A at 4 kHz for normal duty |
173 A at 4 kHz for heavy duty |
EMC filter |
Integrated |
With EMC plate option |
IP degree of protection |
IP21 |
Degree of protection |
UL type 1 |
option module |
Slot A: communication module for Profibus DP V1 |
Slot A: communication module for PROFINET |
Slot A: communication module for DeviceNet |
Slot A: communication module for EtherCAT |
Slot A: communication module for CANopen daisy chain RJ45 |
Slot A: communication module for CANopen SUB-D 9 |
Slot A: communication module for CANopen screw terminals |
Slot A/slot B/slot C: digital and analog I/O extension module |
Slot A/slot B/slot C: output relay extension module |
Slot B: 5/12 V digital encoder interface module |
Slot B: analog encoder interface module |
Slot B: resolver encoder interface module |
Motor power kW |
110.0 kW for normal duty |
90.0 kW for heavy duty |
Asynchronous motor control profile |
Constant torque standard |
Variable torque standard |
Optimized torque mode |
Synchronous motor control profile |
Permanent magnet motor |
Synchronous reluctance motor |
Maximum output frequency |
599 Hz |
Switching frequency |
1…8 kHz adjustable |
2.5…8 kHz with derating factor |
Nominal switching frequency |
2.5 kHz |
Line current |
201.0 A at 380 V (normal duty) |
170.0 A at 380 V (heavy duty) |
165.0 A at 480 V (normal duty) |
143.0 A at 480 V (heavy duty) |
Apparent power |
121.8 kVA at 380…480 V (normal duty) |
102.6 kVA at 380…480 V (heavy duty) |
Maximum transient current |
253 A during 60 s (normal duty) |
259.5 A during 60 s (heavy duty) |
Network frequency |
50…60 Hz |
Prospective line Isc |
50 kA |
Complementary |
Discrete input number |
10 |
Relay output type |
Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles |
Configurable relay logic R2: sequence relay NO electrical durability 1000000 cycles |
Configurable relay logic R3: sequence relay NO electrical durability 1000000 cycles |
Physical interface |
Ethernet |
2-wire RS 485 |
Connector type |
2 RJ45 |
1 RJ45 |
Method of access |
Slave Modbus TCP |
Transmission rate |
10, 100 Mbits |
4.8 kbps |
9600 bit/s |
19200 bit/s |
Transmission frame |
RTU |
Number of addresses |
1…247 |
Data format |
8 bits, configurable odd, even or no parity |
Type of polarization |
No impedance |
4 quadrant operation possible |
TRUE |
Acceleration and deceleration ramps |
Linear adjustable separately from 0.01…9999 s |
S, U or customized |
Motor slip compensation |
Adjustable |
Automatic whatever the load |
Can be suppressed |
Not available in permanent magnet motor law |
Braking to standstill |
By DC injection |
Brake chopper integrated |
TRUE |
Maximum input current |
201.0 A |
Maximum output voltage |
480.0 V |
Relative symmetric network frequency tolerance |
5% |
Base load current at high overload |
173.0 A |
Base load current at low overload |
211.0 A |
With safety function Safely Limited Speed (SLS) |
TRUE |
With safety function Safe brake management (SBC/SBT) |
TRUE |
With safety function Safe Operating Stop (SOS) |
FALSE |
With safety function Safe Position (SP) |
FALSE |
With safety function Safe programmable logic |
FALSE |
With safety function Safe Speed Monitor (SSM) |
FALSE |
With safety function Safe Stop 1 (SS1) |
TRUE |
With sft fct Safe Stop 2 (SS2) |
FALSE |
With safety function Safe torque off (STO) |
TRUE |
With safety function Safely Limited Position (SLP) |
FALSE |
With safety function Safe Direction (SDI) |
FALSE |
Protection type |
Thermal protection: motor |
Safe torque off: motor |
Motor phase break: motor |
Thermal protection: drive |
Safe torque off: drive |
Overheating: drive |
Overcurrent between output phases and earth: drive |
Overload of output voltage: drive |
Short-circuit protection: drive |
Motor phase break: drive |
Overvoltages on the DC bus: drive |
Line supply overvoltage: drive |
Line supply undervoltage: drive |
Line supply phase loss: drive |
Overspeed: drive |
Break on the control circuit: drive |
Quantity per set |
1 |
Width |
320 mm |
Height |
1205 mm |
Depth |
393 mm |
Net weight |
104 kg |
Electrical connection |
Line side: screw terminal 2 x 50…3 x 120 mm²/2 x AWG 1/0…2 x 300 kcmil |
DC bus: screw terminal 0.5…1.5 mm²/AWG 20…AWG 16 |
Control: screw terminal 0.5…1.5 mm²/AWG 20…AWG 16 |
Transmission rate |
10/100 Mbit/s for Ethernet IP/Modbus TCP |
4.8, 9.6, 19.2, 38.4 kbit/s for Modbus serial |
Data format |
8 bits, configurable odd, even or no parity for Modbus serial |
Type of polarization |
No impedance for Modbus serial |
Number of addresses |
1…247 for Modbus serial |
Local signalling |
Local diagnostic: 3 LEDs (mono/dual colour) |
5 LEDs (dual colour) |
2 LEDs (dual colour) |
1 LED (red) |
Isolation |
Between power and control terminals |
Environment |
Operating position |
Vertical +/- 10 degree |
Product certifications |
UL |
CSA |
TÜV |
Marking |
CE |
Standards |
UL 508C |
IEC 61800-3 |
IEC 61800-5-1 |
IEC 61000-3-12 |
IEC 60721-3 |
IEC 61508 |
IEC 13849-1 |
Maximum THDI |
<48 % full load conforming to IEC 61000-3-12 |
Assembly style |
Enclosed |
Electromagnetic compatibility |
Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 |
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 |
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 |
1.2/50 µs – 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 |
Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 |
Environmental class (during operation) |
Class 3C3 according to IEC 60721-3-3 |
Class 3S3 according to IEC 60721-3-3 |
Maximum acceleration under shock impact (during operation) |
150 m/s² at 11 ms |
Maximum acceleration under vibrational stress (during operation) |
10 m/s² at 13…200 Hz |
Maximum deflection under vibratory load (during operation) |
1.5 mm at 2…13 Hz |
Permitted relative humidity (during operation) |
Class 3K5 according to EN 60721-3 |
Overvoltage category |
III |
Regulation loop |
Adjustable PID regulator |
Insulation resistance |
> 1 MOhm 500 V DC for 1 minute to earth |
Noise level |
69.9 dB conforming to 86/188/EEC |
Vibration resistance |
1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-6 |
1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6 |
Shock resistance |
6 gn for 11 ms conforming to IEC 60068-2-27 |
Environmental characteristic |
Chemical pollution resistance class 3C3 conforming to IEC 60721-3-3 |
Dust pollution resistance class 3S3 conforming to IEC 60721-3-3 |
Relative humidity |
5…95 % without condensation conforming to IEC 60068-2-3 |
Ambient air temperature for operation |
-15…50 °C (without derating) |
50…60 °C (with derating factor) |
Noise level |
69.9 dB |
pollution degree |
2 |
Ambient air transport temperature |
-25…70 °C |
Ambient air temperature for storage |
-25…70 °C |
Packing Units |
Unit Type of Package 1 |
PCE |
Number of Units in Package 1 |
1 |
Package 1 Height |
71.000 cm |
Package 1 Width |
50.000 cm |
Package 1 Length |
141.000 cm |
Package 1 Weight |
128.000 kg |
Logistical informations |
Country of origin |
CN |