| Parameter Item | Official Specification Value |
|---|---|
| Full Model Number | CIMR-AD4A0038FMA |
| Product Series | A1000 High Performance Vector Control AC Drive |
| Voltage Class | 400V Class (3-phase 380–480 VAC) |
| Model Code Definition | AD: Standard chassis, no built-in EMC filter; 4:400V; 0038: Rated output current 38A; F: IP20/NEMA1 enclosure; MA: Standard spec, no encoder option |
| Rated Output Current (ND Normal Duty) | 38 A |
| Rated Output Current (HD Heavy Duty) | 31 A |
| Max Applicable Motor Power (ND) | 18.5 kW |
| Max Applicable Motor Power (HD) | 15 kW |
| Input Power Spec | 3-phase AC 380–480 V, 50/60 Hz; allowable voltage fluctuation -15% ~ +10% |
| Max Output Voltage | 3-phase 0–480 VAC |
| Adjustable Output Frequency Range | 0–400 Hz |
| Carrier Frequency | 2–15 kHz user configurable |
| Overload Capacity | ND: 120% rated current for 60s; HD: 150% rated current for 60s |
| Control Modes | Open-loop V/F, Closed-loop V/F, Open-loop vector, Closed-loop vector, PM motor vector control |
| Built-in Brake Transistor | External brake resistor required (no internal brake transistor) |
| Standard Control I/O Terminals | 8 multi-function digital inputs (24 VDC); 3 analog inputs; 1 pulse input; 4 relay digital outputs; 2 analog outputs; 1 pulse output |
| Safety Function | STO Safe Torque Off, SIL2 / PL d safety compliance |
| Communication Interfaces | Standard RS485 (Modbus RTU); expandable via option cards: Profibus-DP, DeviceNet, Ethernet/IP, Profinet |
| Cooling Type | Forced air cooling |
| Enclosure Protection Grade | IP20 / NEMA Type 1 |
| Overall Dimensions (W × H × D) | 180 mm × 300 mm × 187 mm |
| Net Weight | 5.7 kg |
| Operating Ambient Temperature | -10 °C ~ +40 °C full load; -10 ~ +50 °C with power derating |
| Storage & Transport Temperature | -20 °C ~ +60 °C |
| Relative Humidity | 5%–95% RH, non-condensing |
| Altitude Limit | 0–1000 m full power; derate 1% per 100 m up to max 3000 m |
| Vibration Resistance | 10–20 Hz: 9.8 m/s²; 20–55 Hz: 5.9 m/s² |
| Built-in DC Reactor | Not equipped, external DC reactor recommended for harmonic suppression |
| EMC Filter | No built-in EMC filter (external filter required for CE EMC compliance) |
| Supported Motor Types | 3-phase induction motor, permanent magnet synchronous motor |
| Hardware Protection | Overcurrent, overvoltage, undervoltage, overheat, motor overload, earth fault, output short circuit |
| Global Certifications | UL, cUL, CE, UKCA, RoHS 2.0 compliant |