A1000 inverter: 3~ 400 V, HD: 110 kW 216 A, ND: 132 kW 250 A, max. output freq. 400Hz
Specifications
CIMR-AC4A0250AAA
| Parameter Item | Official Specification Value |
|---|---|
| Full Model Number | CIMR-AC4A0250AAA |
| Product Series | A1000 High Performance Vector Control AC Drive |
| Cooling Structure | Finless Cold Plate Type (Fanless design) |
| Enclosure Protection Class | IP00 (Chassis-mounted, installed inside cabinet) |
| Built-in EMC Filter | Equipped with integrated EMC filter |
| Input Power Supply | 3-phase AC 380–480 V, 50 / 60 Hz |
| Inverter Control Modes | Closed loop V/f, Closed loop vector, Open loop V/f, Open loop vector |
| Rated Output Current (ND Normal Duty) | 250 A |
| Rated Output Current (HD Heavy Duty) | 216 A |
| Max Applicable Motor Power (ND Variable Torque) | 132 kW |
| Max Applicable Motor Power (HD Constant Torque) | 110 kW |
| Overload Capacity | ND: 120% rated current for 60 s; HD: 150% rated current for 60 s |
| Max Adjustable Output Frequency | 0.01 – 400 Hz |
| Compatible Motor Types | Induction/asynchronous motor, Permanent magnet synchronous motor |
| Regenerative Solution Support | Realized via optional external braking unit |
| Standard Onboard Communication Ports | MODBUS Slave, Serial RS-422, Serial RS-485 |
| Optional Communication Cards | CANopen, DeviceNet Slave, EtherCAT Slave, EtherNet/IP, MECHATROLINK II Slave, MODBUS/TCP, POWERLINK, PROFIBUS DP Slave, PROFINET Slave |
| Standard I/O Terminals | 8 multi-function digital inputs, 3 analog inputs, 1 pulse input, 4 relay digital outputs, 2 analog outputs, 1 pulse output |
| Safety Function | STO Safe Torque Off, SIL 2 / PL d compliant |
| Braking Transistor | No built-in braking transistor, external braking unit required |
| Overall Dimensions (W × H × D) | 500 mm × 800 mm × 350 mm |
| Net Weight | 96 kg |
| Continuous Operating Ambient Temp | -10 °C ~ +40 °C full load; -10 °C ~ +50 °C with power derating |
| Storage & Transport Temperature | -20 °C ~ +60 °C |
| Relative Humidity | 5% – 95% RH, non-condensing, no icing |
| Installation Altitude | Full power up to 1000 m; derate 1% per 100 m, max 3000 m |
| Vibration Resistance | 10–20 Hz: 9.8 m/s²; 20–55 Hz: 5.9 m/s² |
| Global Certifications | UL, cUL, CE, UKCA, RoHS 2.0 compliant |